2 MW PV Battery Grid System
2 MW PV Battery Grid System
𝐈𝐧𝐭𝐫𝐨𝐝𝐮𝐜𝐭𝐢𝐨𝐧
The 2 MW PV Battery Grid System in MATLAB/Simulink demonstrates the integration of a large-scale solar photovoltaic source, battery energy storage, utility grid, and AC load through a common power conversion system.

The simulation is designed to study:
2 MW solar PV power generation
Battery charging and discharging
Grid power import and export
DC-link power management
Grid-connected inverter control
dq-axis current control
Active power injection
Harmonic performance
System response under changing solar irradiance
Continuous power supply to the connected load
The model is useful for students, researchers, and engineers studying renewable energy integration, battery energy storage, grid-connected converters, and power management using MATLAB/Simulink.
𝐒𝐲𝐬𝐭𝐞𝐦 𝐎𝐯𝐞𝐫𝐯𝐢𝐞𝐰
The complete system contains four major power sections:
Solar PV array
Battery energy storage system
Three-phase utility grid
Three-phase AC load
The PV source and battery are connected to a common DC link, while a grid-connected inverter transfers power between the DC side and the point of common coupling.
Main System Parameters
Parameter | Value / Description |
Grid capacity | 154 MW |
Grid voltage | 34.5 kV |
Transformer output | 400 V |
Solar PV capacity | Approximately 2 MW |
AC load | Approximately 1.5 MW |
Battery nominal voltage | Approximately 300 V |
PV connection | Directly connected to DC link |
Battery connection | Through bidirectional DC–DC converter |
Grid interface | Three-phase inverter |
Reactive power reference | 0 |
Nominal test irradiance | 1000 W/m² |
PV temperature | 25°C |
𝐒𝐲𝐬𝐭𝐞𝐦 𝐀𝐫𝐜𝐡𝐢𝐭𝐞𝐜𝐭𝐮𝐫𝐞
The power flow structure can be summarized as:
Solar PV → DC Link → Grid Inverter → PCC → Grid and Load
The battery is connected as:
Battery ↔ Bidirectional DC–DC Converter ↔ DC Link
This configuration allows the battery to operate in both directions.
Battery Charging Mode
When sufficient PV power is available:
PV supplies the load.
Excess renewable energy can charge the battery.
Battery current becomes negative according to the adopted charging convention.
Battery state of charge gradually increases.
Battery Discharging Mode
When PV generation falls:
Battery supplies additional power to the DC link.
Battery current becomes positive.
Stored battery energy supports the connected load.
The utility grid provides the remaining power whenever required.
𝐒𝐨𝐥𝐚𝐫 𝐏𝐕 𝐀𝐫𝐫𝐚𝐲
The model uses a large PV array designed to produce approximately 2 MW under standard operating conditions.
PV Array Configuration
PV Parameter | Approximate Value |
Single-module rated power | 404 W |
Voltage at maximum power point | 72.9 V |
Current at maximum power point | 5.6 A |
Modules connected in series per string | 7 |
Parallel strings | Approximately 712 |
Total array capacity | Approximately 2 MW |
Standard irradiance | 1000 W/m² |
Standard temperature | 25°C |
At high irradiance, the PV array supplies a large portion of the load requirement and can also provide energy for battery charging.
𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐄𝐧𝐞𝐫𝐠𝐲 𝐒𝐭𝐨𝐫𝐚𝐠𝐞
The battery is connected to the common DC link through a bidirectional DC–DC converter.
This converter provides controlled power transfer in both directions.
Main Functions of the Battery
Store surplus PV energy
Support the DC link during reduced solar generation
Reduce sudden grid power demand
Improve power balance
Supply additional power during low irradiance
Support continuous load operation
The battery nominal voltage is approximately 300 V.
For a megawatt-scale system, the required battery current capability is very high. Therefore, practical implementation normally requires multiple battery strings or modules connected in suitable series-parallel combinations.
𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐂𝐮𝐫𝐫𝐞𝐧𝐭 𝐂𝐨𝐧𝐭𝐫𝐨𝐥
A controlled reference current is generated for the battery converter.
The battery controller performs the following process:
PV operating information is measured.
A suitable battery current reference is generated.
The reference current is compared with actual battery current.
The current error is processed by a PI controller.
The controller generates the required duty command.
A PWM generator produces switching pulses.
The bidirectional converter controls battery charging or discharging.
This approach allows the battery current to automatically change according to renewable power availability.
𝐃𝐂-𝐋𝐢𝐧𝐤 𝐚𝐧𝐝 𝐈𝐧𝐯𝐞𝐫𝐭𝐞𝐫
The DC link acts as the common energy interface between:
Solar PV
Battery system
Grid-connected inverter
The inverter converts the DC-link power into three-phase AC power suitable for the point of common coupling.
An output filter is included to reduce switching harmonics before the inverter power reaches the grid.
𝐂𝐨𝐧𝐭𝐫𝐨𝐥 𝐒𝐭𝐫𝐚𝐭𝐞𝐠𝐲
The grid-side converter uses a synchronous dq-axis control technique.
The major control stages are:
DC-link/reference voltage processing
Active current reference generation
Reactive current reference selection
Three-phase voltage and current measurement
Phase-Locked Loop
abc-to-dq transformation
dq-axis current control
Feedforward and decoupling compensation
dq-to-abc inverse transformation
PWM pulse generation
𝐏𝐡𝐚𝐬𝐞-𝐋𝐨𝐜𝐤𝐞𝐝 𝐋𝐨𝐨𝐩
A PLL synchronizes the inverter controller with the three-phase utility grid.
The PLL provides the electrical angle required for coordinate transformations.
It supports:
Accurate grid synchronization
abc-to-dq transformation
dq-to-abc transformation
Stable current control
Controlled real and reactive power transfer
𝐝𝐪-𝐀𝐱𝐢𝐬 𝐂𝐮𝐫𝐫𝐞𝐧𝐭 𝐂𝐨𝐧𝐭𝐫𝐨𝐥
The measured three-phase voltage and current signals are transformed into the rotating reference frame.
The controller produces:
d-axis current
q-axis current
In this model:
Id reference is used mainly for real power control.
Iq reference is maintained at zero.
Therefore, the inverter is primarily commanded to transfer active power, while reactive power injection is kept close to zero under the selected operating strategy.
𝐅𝐞𝐞𝐝𝐟𝐨𝐫𝐰𝐚𝐫𝐝 𝐚𝐧𝐝 𝐃𝐞𝐜𝐨𝐮𝐩𝐥𝐢𝐧𝐠 𝐂𝐨𝐧𝐭𝐫𝐨𝐥
The d-axis and q-axis current errors are processed through PI controllers.
Feedforward and decoupling terms are included to improve:
Current tracking
Dynamic response
d-axis and q-axis independence
Grid voltage disturbance rejection
Active power control
The resulting voltage references are converted back into three-phase quantities and sent to the PWM modulator.
𝐏𝐖𝐌 𝐆𝐞𝐧𝐞𝐫𝐚𝐭𝐢𝐨𝐧
The three-phase reference voltage signals are supplied to the PWM stage.
The PWM generator creates switching signals for the grid-side power converter.
This controls:
Inverter output voltage
Grid current
Active power transfer
DC-link energy transfer
𝐌𝐞𝐚𝐬𝐮𝐫𝐞𝐝 𝐏𝐚𝐫𝐚𝐦𝐞𝐭𝐞𝐫𝐬
The MATLAB/Simulink model continuously monitors important electrical parameters.
PV Measurements
Solar irradiance
PV voltage
PV current
PV power
Battery Measurements
Battery voltage
Battery current
Battery power
Battery State of Charge
Load Measurements
Three-phase voltage
Three-phase current
Active power
Current THD
Grid Measurements
Three-phase grid voltage
Three-phase grid current
Grid active power
Current THD
𝐒𝐢𝐦𝐮𝐥𝐚𝐭𝐢𝐨𝐧 𝐑𝐞𝐬𝐮𝐥𝐭𝐬
The system is tested under different solar irradiance levels to evaluate PV generation, battery operating mode, and grid contribution.
Case 1 — Irradiance of 1000 W/m²
At standard solar irradiance:
Parameter | Approximate Result |
Irradiance | 1000 W/m² |
PV power | 2 MW |
PV voltage | Around 500 V |
PV current | Around 4000 A |
Battery current | Around −200 A |
Battery power | Around −60 kW |
Battery condition | Charging |
Load power | Approximately 1.5 MW |
The negative battery power indicates charging under the adopted sign convention.
The available PV generation is sufficient to supply the major load demand while also supporting battery charging.
Case 2 — Irradiance of 500 W/m²
When irradiance is reduced to approximately 500 W/m², PV generation decreases significantly.
Parameter | Approximate Result |
Irradiance | 500 W/m² |
PV power | Approximately 1 MW |
Battery current | Around 280 A |
Battery power | Approximately 100 kW |
Battery condition | Discharging |
Grid contribution | Approximately 450 kW import |
Load power | Approximately 1.5 MW |
In this condition:
PV generation is insufficient to meet the complete load.
Battery changes from charging to discharging mode.
The utility grid supplies the remaining load requirement.
The AC load continues receiving approximately its rated power.
Case 3 — Very Low Solar Irradiance
The system is also examined under very low solar availability.
Parameter | Approximate Result |
Irradiance | Around 50 W/m² |
PV power | Around 100 kW |
Battery power | Around 200 kW discharge |
Grid import | Around 1.2 MW |
Load power | Approximately 1.5 MW |
Battery condition | Discharging |
Under this operating condition:
PV output becomes very low.
Battery supplies part of the required energy.
Grid import increases considerably.
The load remains continuously supplied.
This demonstrates coordinated operation between PV, battery, and utility grid.
𝐎𝐩𝐞𝐫𝐚𝐭𝐢𝐧𝐠 𝐌𝐨𝐝𝐞 𝐂𝐨𝐦𝐩𝐚𝐫𝐢𝐬𝐨𝐧
Solar Condition | PV Contribution | Battery Mode | Grid Role |
High irradiance | High | Charging | Low contribution / possible export |
Medium irradiance | Medium | Discharging | Supplies deficit power |
Very low irradiance | Low | Discharging | Major power supplier |
The system automatically redistributes power according to available solar generation.
𝐏𝐨𝐰𝐞𝐫 𝐁𝐚𝐥𝐚𝐧𝐜𝐞 𝐁𝐞𝐡𝐚𝐯𝐢𝐨𝐮𝐫
One of the main objectives of the model is maintaining power balance at the point of common coupling.
When PV generation changes:
Battery power automatically changes.
Grid contribution adjusts.
Load demand remains approximately constant.
DC-side and AC-side power flows remain coordinated.
This makes the model useful for understanding renewable-energy power management under changing environmental conditions.
𝐇𝐚𝐫𝐦𝐨𝐧𝐢𝐜 𝐏𝐞𝐫𝐟𝐨𝐫𝐦𝐚𝐧𝐜𝐞
THD measurement blocks are included for monitoring current quality.
The simulation shows:
Three-phase grid current with near-sinusoidal behaviour
Three-phase grid voltage with balanced sinusoidal waveform
Filtered inverter output
Load-current harmonic monitoring
Grid-current harmonic monitoring
The exact THD value depends on simulation settings, converter switching conditions, measurement window, and FFT configuration.
𝐊𝐞𝐲 𝐅𝐞𝐚𝐭𝐮𝐫𝐞𝐬
2 MW grid-connected solar PV system
Large-scale battery energy storage integration
154 MW, 34.5 kV utility grid
34.5 kV to 400 V transformer
Approximately 1.5 MW AC load
Bidirectional battery converter
Battery charging and discharging control
Common DC-link architecture
Three-phase grid inverter
PLL-based grid synchronization
abc-to-dq transformation
dq-to-abc transformation
PI current control
Feedforward and decoupling compensation
Zero reactive-current reference operation
PWM-based inverter switching
Harmonic filtering
Grid-current THD monitoring
Load-current THD monitoring
Variable irradiance testing
PV, battery, grid, and load power monitoring
𝐖𝐡𝐚𝐭 𝐂𝐚𝐧 𝐁𝐞 𝐋𝐞𝐚𝐫𝐧𝐞𝐝 𝐅𝐫𝐨𝐦 𝐓𝐡𝐢𝐬 𝐌𝐨𝐝𝐞𝐥?
This MATLAB/Simulink model provides a clear understanding of:
Large-scale PV array design
Battery-grid coordination
Renewable power fluctuations
Grid power import and export
Battery charging and discharging
DC-link energy management
Three-phase inverter operation
PLL synchronization
Reference-frame transformations
Active and reactive current control
Grid-side PWM control
Harmonic monitoring
Power balance under changing irradiance
𝐀𝐩𝐩𝐥𝐢𝐜𝐚𝐭𝐢𝐨𝐧𝐬
The concepts demonstrated in this simulation are applicable to:
Grid-connected solar power plants
Battery Energy Storage Systems
Solar-plus-storage systems
Industrial renewable energy systems
Smart grids
Microgrids
Distributed generation systems
Utility-scale PV integration
Energy management studies
Grid-connected converter research
Renewable power-quality analysis
𝐂𝐨𝐧𝐜𝐥𝐮𝐬𝐢𝐨𝐧
The 2 MW PV Battery Grid System in MATLAB/Simulink demonstrates coordinated operation of solar PV generation, battery storage, a utility grid, and a large AC load.
The simulation clearly shows that:
At high irradiance, PV generation reaches approximately 2 MW, allowing the battery to charge.
At medium irradiance, PV output decreases and the battery begins discharging while the grid supplies the remaining power.
At very low irradiance, the grid becomes the major source while the battery provides additional support.
The connected load continues receiving power despite substantial changes in solar generation.
The dq-based inverter controller enables controlled real-power exchange with the utility grid.
Overall, the model provides a practical MATLAB/Simulink platform for studying large-scale solar PV integration, battery energy management, grid-connected inverter control, power balance, and renewable energy system performance.